U7698E Flame Detector
15
Part 334614E
E 2002 Nordson Corporation
Manual 34-49
Major Fault Mode
The system goes into major fault mode when faults are detected in both
detector heads, preventing the detection of a fire.
WARNING: Immediately correct any condition that causes a fault or major
fault. Do not operate the coating system with the flame detector shut down
or bypassed, or with a malfunctioning flame detector component.
In major fault mode,
S both amber DET. HEAD FAULT indicators light.
S the FAULT DETECTED alarm turns on (continuous tone).
S the booth fire interlock opens, shutting down the booth and application
equipment.
S the conveyor continues to run.
NOTE: If only one detector head is installed, any fault is treated as a major
fault.
When the fault is corrected, the fault indicator(s) and alarm turn off and
Normal mode resumes.
Fire Mode
When a fire is detected,
S the red FIRE DETECTED indicator turns on.
S the FIRE DETECTED alarm turns on (fast intermittent tone).
S booth and conveyor interlock relays open. The booth, application
equipment, and conveyor will shut down.
S fire interlock contact (customer use) changes state. Customer use
equipment is either activated or deactivated, depending on use.
Reset
To reset a detector head after a fault has been corrected, move the DET.
HEAD RESET switch toward the appropriate detector head fault indicator,
then release it.
Through-the-Lens Test
The detector heads automatically perform periodic through-the-lens tests to
check their operation. If a test fails, the detector head goes into fault mode.
Refer to Troubleshooting for diagnostic and correction procedures.